Alicante, Spain

Hotel | 96 sqm installation


 


Project summary Technical description Financing Development Downloads

Project Summary

Description
The installation is formed by 48 SOLAHART collectors, mod. L, situated in a suitable area. The 48 collectors are divided into 8 batteries of 6 collectors. The system uses a variable temperature control which operates the primary and secondary circuits.
The collector heat is transferred to the storage tank by an external heat exchanger. The variable temperature setting to start/stop the circulation pumps is 6 C.
System use: ACS with a solar fraction of 80 %.

 

 


Building

Type of building

Hotel

Number of users / dwellings, floors

60 users
100 rooms

Year of construction

2004

Total effective area (heated)

not available 

Hot tap water consumption (measured/estimated)

not available

Whole energy consumption for heating purpose after CSTS implementation

30,871 kWh/a


System engineering

Year of construction of CSTS

2004

Type of collectors

Flat plate collectors

Thermal power

62.5 kWtherm.

Aperture area of collectors*)

89.28 m2

Buffer storage

5 m3

Hot tap water storage

not available 

Total capacity of boilers with energy source

75 + x kW,

Type of hot tap water heating

Centralised

Type of heating system

Centralised


Costs

Total cost solar system

56,155 Euro

Cost of the CSTS / gross area of collectors

585 Euro/m2

Subsidies

30 %


Output

Output of solar heat**)

50,424 kWh/a

Reduction of final energy***)

72,034 kWh/a

CO2-emissions avoided

16.5 CO2/a

Solar performance guarantee

*) Aperture area = light transmitting area of the front glass
**) measured, between storage and piping to taps (solar system output)
***) related to the measured output mentioned before

 


 


Operator (ESCo)

Instalaciones Gallego Blaya S.L.
I. Albeniz, 3
03580 Alfas Pi
Alicante, Spain
Phone: 966865164

Top of page Project summary Technical description Financing Development Downloads

Technical description

 


Description of the CSTS

Year of construction of CSTS

2004

Thermal power

62 kWtherm.

Gross area of collectors

96 m2

Aperture area of collectors

89.28 m2 

Type of collectors

Flat plate collectors

Type of assembly

On flat roof

Orientation of collectors

South (0)

Inclination angle to horizon

45

Freezing protection

Glycol

Overheating protection

Expansion vessel

Operation mode

Low flow

Use of CSTS for

Hot tap water heating

Buffer storage

5 m3 (1 5 m3)

Hot tap water storage

not available 

Control of backup-system / CSTS

Separated control


Hot tap water system

Type of hot water heating

Centralised

Recirculation system

Yes

For decentralised systems:
The installation on the consumer site

./.

Size of storage for hot tap water

not available 

Specification (if necessary)

Separated back-up heater/boiler for hot water heating only: standard, natural gas, 2003, capacity not available


Space heating system

Type of heating system

Centralised

Number of boilers

1

Total capacity (power output) of boilers

75 kW

Capacity of each boiler (year of construction)

No. 1: kW (2003)

Energy source

Natural gas

Type of boiler system

Standard


Type of operation

Operator of the CSTS system

ESCo

CSTS monitoring

Yes: output of solar heat

Data accessible via internet

No

Scientific monitoring / follow up

Yes

Maintenance contract

Yes: one to three times a year

Visualisation of the solar heat output

Yes


Yield of CSTS plant

Output of solar heat

50,424 kWh/a

Origin of data

Design (calculated)

Measuring point

Between collector and storage

Reduction of final energy

72,034 kWh/a

Origin of data

Designed data

Solar performance guarantee

Yes


Heat consumption

Whole energy consumption for heating purposes after CSTS implementation

30,871 kWh/a

Origin of data

Estimated

Energy used for

Hot tap water heating

Whole energy consumption for heating purposes before CSTS implementation

102,906 kWh/a

Total tap water consumption

2,190 m3/a

Hot tap water consumption

not available

Hot tap water temperature

45 C

Cold water temperature

12.3 C

 

 


Summary

The installation is formed by 48 SOLAHART collectors, mod. L, situated in a suitable area.The 48 collectors are divided into 8 batteries of 6 collectors. The system uses a variable temperature control which operates the primary and secondary circuits.

The collector heat is transferred to the storage tank by an external heat exchanger. The variable temperature setting to start/stop the circulation pumps is 6 C.

System use: ACS with a solar fraction of 80%.



 


Collectors' provider

SACLIMA S.L.
Elena Salazar Mir
Pol. Ind. "Els Mollons
C/Torners, 21
46970 Alaquas (Valencia), Spain
Phone: +34 96 151 61 62
Fax: +34 96 151 22 88
info(at)saclima.com
www.saclima.es


Collectors' manufacturer

Solarhart industries
Rob meesters
Vlamoven weg 12
5708JV Helmond, Netherlands
Phone: +31 492579696
Fax: +31 492579694
r.meesters(at)solahart-europe.com
www.solahart.com

Top of page Project summary Technical description Financing Development Downloads

Financing and investment

 


Financing of the CSTS

Form of financing

Purchase

Distribution in percentage

20 % loans
30 % subsidies (granted by the Valencia Energy Agency)


Costs of solar materials

Total cost of solar system

56,155 Euro

Detailed costs for

Collectors

22,000 Euro

Elevation / mounting structure

3,128 Euro

Storage / heat exchanger

6,500 Euro

Backup heater

./.

Control

540 Euro

Installation

21,752 Euro

Planning / Engineering

./.

Others (system of pumping)

2,235 Euro


Operation costs of heating system

Increase of the operation cost after CSTS implementation

not available

 

 


Top of page Project summary Technical description Financing Development Downloads

Development & experiences

 


Experiences management

Experienced problems or failures?

No

Found solutions to these problems or failures?

./.


Financial effects / project performance

Project economically efficient?

Yes:
The investment will generate considerable savings in a medium term to the hotel owner.

Fiscal or other financial effects?

No

Effects on rental fees?

No


Experiences technical staff

Experienced problems or failures?

No

Found solutions to these problems or failures?

./.

 


Top of page Project summary Technical description Financing Development Downloads

Downloads

PDF datasheet coming soon