Project Summary

Description
The complete restructuring and conversion of existing rural buildings into a residential complex was conceived to combine best building practice with well accepted and experimented energy saving measures. The installation of solar panels for hot water production was an obvious initial choice. High standard thermal insulation, efficient low temperature central heating coupled with individual energy metering to encourage savings, rainwater collection for garden irrigation, are among the other features accompanying the solar thermal water heating system.

 


Building

Type of building

Multi-family house

Number of users / dwellings, floors

45 users
12 dwellings
3 floors

Year of construction

2006

Total effective area (heated)

1,300 m2

Hot tap water consumption (measured/estimated)

not available

Whole energy consumption for heating purpose after CSTS implementation

33,500 kWh/a


System engineering

Year of construction of CSTS

2007

Type of collectors

Flat plate collectors

Thermal power

28 kWtherm.

Aperture area of collectors*)

40 m2

Buffer storage

2 m3

Hot tap water storage

1 m3

Total capacity of boilers with energy source

187 kW,

Type of hot tap water heating

Centralised

Type of heating system

Centralised


Costs

Total cost solar system

32,155 Euro

Cost of the CSTS / gross area of collectors

ca. 580 Euro/m2

Subsidies

0 %


Output

Output of solar heat**)

24,000 kWh/a

Reduction of final energy***)

32,000 kWh/a

CO2-emissions avoided

7.4 CO2/a

Solar performance guarantee

No

*) Aperture area = light transmitting area of the front glass
**) measured, between storage and piping to taps (solar system output)
***) related to the measured output mentioned before

 

 


Ing. Piero Balossi:

"The initial decision was taken after an analysis at feasibility study level, considering the investment costs and the expected energy outputs for different combinations of panel surface and storage capacity. For instance, a solar contribution to the heating system was discarded due to excessive storage capacity needed.
Rather than contracting to a general contractor, the project was organised through a self-construction agreement assisted by a specialised ecological co-operative association. This permitted to select and purchase the most economical equipment directly from the manufacturers on the international market and, most important, to maximise the direct involvement of the owner to the wider perspective of the responsible use of energy and natural resources."

 

 


Owner

Piero Balossi
via Piave 9
Olgiate Olona (VA), Italy
Phone: +39 3486507188
Fax: +39 0331376188
balossi(at)mclink.it
www.podererestelli.it


Operator

See owner

Top of page Project summary · Technical description · Financing · Development · Downloads

Technical description

 


Description of the CSTS

Year of construction of CSTS

2007

Thermal power

28 kWtherm.

Gross area of collectors

not available

Aperture area of collectors

40 m2 

Type of collectors

Flat plate collectors

Type of assembly

Roof-integration

Orientation of collectors

South-West (12°)

Inclination angle to horizon

20°

Freezing protection

Glycol

Overheating protection

Expansion vessel

Operation mode

Low-flow

Use of CSTS for

Hot tap water heating

Buffer storage

2 m3
(one storage tank)

Hot tap water storage

1 m3
(one storage tank)

Control of backup-system / CSTS

Separated control


Hot tap water system

Type of hot water heating

Centralised

Recirculation system

Yes

For decentralised systems:
The installation on the consumer site

./.

Size of storage for hot tap water

1 m3

Specification (if necessary)

./.


Space heating system

Type of heating system

Centralised

Number of boilers

1

Total capacity (power output) of boilers

187 kW

Capacity of each boiler (year of construction)

No. 1: 187 kW (2006)

Energy source

Natural gas

Type of boiler system

Condensing


Type of operation

Operator of the CSTS system

Self-operation

CSTS monitoring

Yes: output of solar heat. The company dealing with the maintenance of the system checks the monthly energy production of the solar thermal system.

Data accessible via internet

No

Scientific monitoring / follow up

No

Maintenance contract

Yes: The plant started operation in summer 2007. A monthly visit for routine maintenance and consumption data collection is carried out.

Visualisation of the solar heat output

No


Yield of CSTS plant

Output of solar heat

24,000 kWh/a

Origin of data

Calculated

Measuring point

Between collector and storage

Reduction of final energy

32,000 kWh/a

Origin of data

Calculated

Solar performance guarantee

No


Heat consumption

Whole energy consumption for heating purposes after CSTS implementation

33,500 kWh/a

Origin of data

Estimated from calculation

Energy used for

Hot tap water heating

Whole energy consumption for heating purposes before CSTS implementation

not available

Total tap water consumption

730 m3/a

Hot tap water consumption

not available

Hot tap water temperature

45 °C

Cold water temperature

10 °C

 

 


Summary

40 square metres of solar collectors are running in five stripes of 8 m2 each. Low-flow at 540 l/h runs into a storage buffer tank of 2,000 liters, which is heating a boiler of 1,000 liters, which is also connected to a burner at the upper heat exchanger.




Click image for larger view!

 


Planning/Engineering

Rete per l‘autocostruzione del solare termico
Bruno Tommasini
via Scarzara 35
Parma, Italy
Phone: +39 0521 981764
Fax: +39 0521 981764

bruno.tommasini
(at)autocostruzionesolare.it

www.autocostruzionesolare.it

Top of page Project summary · Technical description · Financing · Development · Downloads

Financing and investment

 


Financing of the CSTS

Form of financing

Purchase

Distribution in percentage

0 %
(no subsidies obtained)


Costs of solar materials

Total cost of solar system

23,155 Euro
(incl. VAT of 10 %)

Detailed costs for

Collectors

7,000 Euro

Elevation / mounting structure

./.

Storage / heat exchanger

7,500 Euro

Backup heater

./.

Control

500 Euro

Installation

4,500 Euro

Planning / Engineering

1,500 Euro

Others

./.


Operation costs of heating system

Or:
Increase of the operation cost after CSTS implementation

not available

 




The present 'incentive' regulations in Italy allow a fiscal deduction of up to 55 % of energy saving installations to be spread over three years.


Top of page Project summary · Technical description · Financing · Development · Downloads

Development & experiences

 


Experiences management

Experienced problems or failures?

not available

Found solutions to these problems or failures?

./.


Financial effects / project performance

Project economically efficient?

not available

Fiscal or other financial effects?

not available

Effects on rental fees?

not available


Experiences technical staff

Experienced problems or failures?

not available

Found solutions to these problems or failures?

./.

 



Before the present intervention, in 2003/04, a 12 sqm solar panel for hot water production had been installed in an adjacent two-apartment building. The system has been operated with satisfaction by the tenants. The opportunity to experiment the same solution, but at a larger scale, is really what has triggered the present initiative.

Top of page Project summary · Technical description · Financing · Development · Downloads

Downloads

SOLARGE_goodpractice_it_viatovo.pdf

this datasheet in printable PDF-format

0.9 M

viatovo_scheme.pdf

the hydraulic scheme

787 K

Top of page Project summary · Technical description · Financing · Development · Downloads

Photo gallery